VAF-GRD : 300V
PVC
INSULATED AND SHEATHED FLAT TYPE, WITH GROUND. |
|
|
NUMBER OF CORE |
: 2-3 cores with safety-ground |
CONDUCTOR |
: Solid and stranded annealed copper, |
|
Size 1 mm2 up to 35 mm2 |
GROUND WIRE |
: Ground conductor size 1 mm2 up to 10
mm2. |
INSULATION |
: PVC |
COLOUR |
: 2 core-Light grey, Black. |
|
: 3 core-Light grey, Black, Red. |
|
: Ground core-Green/Yellow |
SHEATH |
: PVC. |
COLOUR |
: White. |
CLASSIFICATION |
: Maximum conductor temperature C. |
|
Circuit voltage not exceeding 300 volts. |
TESTING VOLTAGE |
: 2,000 volts. |
REFERENCE |
: TIS 11-2531, Table 11 |
|
|
|
|
|
|
VAF-GRD
|
|
|
TIS 11-2531
|
|
|
TABLE 11
|
|
|
Number
|
Nominal
|
Number
|
Insulation
|
Nominal
|
Ground
|
Sheath
|
Approx. overall
|
Minimum
|
Maximum
|
Cable
|
Standard
|
of
|
cross
|
and
|
thickness
|
cross
|
insulation
|
thickness
|
diameter(mm)
|
insulation
|
continuous
|
weight
|
length
|
core
|
sectional
|
diameter
|
|
sectional
|
thickness
|
|
Lower limits
|
Uper limit
|
resistance at
|
current rating
|
(approx.)
|
|
|
area
|
of wire
|
|
area of
|
|
|
|
|
|
in free air
|
|
|
|
|
|
|
ground
|
|
|
|
|
|
|
|
|
|
|
|
|
conductor
|
|
|
|
|
|
|
|
|
|
(mm2)
|
(No./mm)
|
(mm)
|
(mm2)
|
|
(mm)
|
|
|
|
(Ampere)
|
(kg/km)
|
(m)
|
2
|
|
|
|
|
|
|
|
|
|
|
|
|
1
|
1/1.13
|
0.6
|
1
|
0.6
|
0.9
|
4.0x8.4 |
4.8x10.0
|
0.0115
|
11
|
75
|
100/C
|
1
|
7/0.43
|
0.6
|
1
|
0.6
|
0.9
|
4.0x8.6 |
5.0x10.5
|
0.0110
|
11
|
80
|
100/C
|
1.5
|
1/1.38
|
0.6
|
1
|
0.6
|
1.2
|
4.8x9.4 |
5.8x11.5
|
0.0100
|
15
|
100
|
100/C
|
1.5
|
7/0.53
|
0.6
|
1
|
0.6
|
1.2
|
4.9x9.8 |
6.0x12.0
|
0.0094
|
15
|
110
|
100/C
|
2.5
|
1/1.78
|
0.7
|
1.5
|
0.6
|
1.2
|
5.4x10.5 |
6.4x13.0
|
0.0092
|
20
|
140
|
100/C
|
2.5
|
7/0.67
|
0.7
|
1.5
|
0.6
|
1.2
|
5.6x11.5 |
6.8x14.0
|
0.0084
|
20
|
140
|
100/C
|
4
|
1/2.25
|
0.8
|
2.5
|
0.6
|
1.2
|
6.0x12.5
|
7.2x15.0
|
0.0086
|
27
|
190
|
100/C
|
4
|
7/0.85
|
0.8
|
2.5
|
0.6
|
1.2
|
6.2x13.0 |
7.6x16.0
|
0.0078
|
27
|
150
|
100/C
|
6
|
7/1.04
|
0.8
|
4
|
0.6
|
1.2
|
6.8x15.0 |
8.2x17.5
|
0.0066
|
35
|
210
|
100/C
|
10
|
7/1.35
|
0.9
|
4
|
0.6
|
1.2
|
8.0x17.0 |
9.4x20.0
|
0.0059
|
49
|
380
|
100/C
|
16
|
7/1.70
|
1.0
|
6
|
0.6
|
1.2
|
9.2x20.0 |
11.0x23.0
|
0.0053
|
65
|
550
|
100/C
|
25
|
7/2.14
|
1.2
|
6
|
0.6
|
1.4
|
11.0x24.0 |
13.0x27.0
|
0.0051
|
88
|
800
|
500/D
|
35
|
19/1.53
|
1.2
|
10
|
0.6
|
1.4
|
12.0x27.0 |
14.5x31.0
|
0.0043
|
109
|
1,100
|
500/D
|
|
|
|
TISI Permitted to increase the maximum overall diameter by 5% |
|
|
C : Packing in coil. |
|
|