Low Voltage Power Cables >>>
 
 
 
NYCY : 750 V PVC INSULATED AND DOUBLE SHEATHED POWER CABLE, WITH CONCENTRIC CONDUCTORS
   
NUMBER OF CORE : 3 cores.
PHASE CONDUCTOR : Concentric stranded annealed copper wires,
  Sizes, 16 mm2 up to 300 mm2
CONCENTRIC : Annealed copper wires. Sizes 16 mm2 up to 150 mm2
INSULATION : PVC.
COLOUR : Light grey, Black, Red.
SHEATH AND UNDER SHEATH : PVC.
COLOUR : Black
CLASSIFICATION : Maximum conductor temperature C.
  Circuit voltage not exceeding 750 volts.
TESTING VOLTAGE : 2,500 volts.
REFERENCE : TIS 11-2531
 
   
NYCY
   
TIS 11-2531
   
Nominal
Number
Insulation
Under
Sheath
Approx.
Maximum
Minimum
Maximum
Cable
Standard
cross
and diameter
thickness
sheath
thickness
overall
conductor
insulation
continuous
weight
length
sectional area
of wire
thickness
diameter
resistance
resistance
current
(approx.)
(mm2)
(No./mm)
at C
at C
rating in
Phase
Concentric
Phase
Concentric
(mm.)
         
Free air
   
(mm)
(mm)
(mm)
(Ampere)
(kg/km)
(m)
                         
3x25
16
7/2.14
19/1.04
1.3
1.2
2.0
30
0.727
0.0054
88
1,600
500/D
3x35
16
19/1.53
19/1.04
1.3
1.2
2.0
33
0.524
0.0047
107
1,900
500/D
3x50
25
19/1.78
25/1.13
1.5
1.5
2.2
38
0.387
0.0046
130
2,600
500/D
3x70
35
19/2.14
23/1.38
1.5
1.5
2.2
43
0.268
0.0039
162
3,500
500/D
3x95
50
19/2.52
27/1.53
1.7
1.5
2.4
48
0.193
0.0038
201
4,700
500/D
3x120
70
37/2.03
31/1.70
1.7
1.8
2.6
53
0.153
0.0034
233
6,000
500/D
3x150
70
37/2.25
31/1.70
1.9
1.8
2.8
58
0.124
0.0034
266
7,000
300/D
3x185
95
37/2.52
36/1.83
2.1
2.0
3.0
64
0.0991
0.0034
306
9,000
300/D
3x240
120
61/2.25
37/2.03
2.3
2.0
3.2
72
0.0601
0.0033
364
11,500
200/D
3x300
150
61/2.52
41/2.14
2.5
2.2
3.4
79
0.0601
0.0032
417
14,000
200/D
           
 
    D: Packing in drum.
     
   
Norminal
Number
Insulation
Under
Sheath
Approx.
Maximum
Minimum
Maximum
Cable
Standard
cross
and diameter
thickness
sheath
thickness
overall
conductor
insulation
continuous
weight
length
sectional area
of wire
thickness
diameter
resistance
resistance
current
(approx.)
(mm2)
(No./mm)
at 20' C
at C
rating in
Phase
Concentric
Phase
Concentric
(mm.)
         
Free air
   
(mm)
(mm)
(mm)
(Ampere)
(kg/km)
(m)
                         
3x16
16
7/1.70
19/1.04
1.1
1.2
2.0
26
1.15
0.0057
66
1,100
500/D
3x25
25
7/2.14
25/1.13
1.3
1.2
2.0
30
0.727
0.0054
88
1,600
500/D
3x35
25
19/1.53
25/1.13
1.3
1.2
2.0
33
0.524
0.0047
107
1,900
500/D
3x50
35
19/1.78
23/1.38
1.5
1.5
2.2
38
0.387
0.0046
130
2,600
500/D
3x70
50
19/2.14
27/1.53
1.5
1.5
2.2
43
0.268
0.0039
162
3,500
500/D
3x95
70
19/2.52
31/1.70
1.7
1.5
2.4
48
0.193
0.0038
201
4,700
500/D
3x120
95
37/2.03
36/1.83
1.7
1.8
2.6
53
0.153
0.0034
233
6,000
500/D
3x150
95
37/2.25
36/1.83
1.9
1.8
2.8
58
0.124
0.0034
266
7,000
300/D
3x150
120
37/2.25
37/2.03
2.1
2.0
3.0
64
0.0991
0.0034
306
9,000
300/D
3x185
120
61/2.52
37/2.03
2.3
2.0
3.2
72
0.0601
0.0033
364
11,500
200/D
           
 
     
    D: Packing in drum.